What is CVE-2018-4843?A medium-severity flaw in Simatic Cp 343-1, explained.
CVE-2018-4843 is a medium-severity flaw (CVSS 6.5) in Simatic Cp 343-1 from Siemens, published on 20 March 2018. It is not on the list of flaws known to be exploited today. The latest forecast puts its chance of use in the next 30 days at 0.5%. If you run an affected version, plan in the vendor’s fix.
Published 20 March 2018. Record last updated 9 May 2023. We keep this page's data up to date.
What is CVE-2018-4843? In plain terms.
An attacker has to be on the same local network without logging in, and nobody has to click anything. If it works, the attacker can take it offline.
A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC CP 343-1 (incl. SIPLUS variants) (All versions), SIMATIC CP 343-1 Advanced (incl. SIPLUS variants) (All versions), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 (All versions < V3.3), SIMATIC CP 443-1 Advanced (All versions < V3.3), SIMATIC ET 200pro IM154-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8F PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200pro IM154-8FX PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIMATIC ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V1.7.0), SIMATIC S7-1500 Software Controller (All versions < V1.7.0), SIMATIC S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIMATIC S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 315T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317T-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 317TF-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319-3 PN/DP (All versions < V3.2.16), SIMATIC S7-300 CPU 319F-3 PN/DP (All versions < V3.2.16), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.7), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.1), SIMATIC WinAC RTX 2010 (All versions < V2010 SP3), SIMATIC WinAC RTX F 2010 (All versions < V2010 SP3), SINUMERIK 828D (All versions < V4.7 SP6 HF1), SIPLUS ET 200S IM151-8 PN/DP CPU (All versions < V3.2.16), SIPLUS ET 200S IM151-8F PN/DP CPU (All versions < V3.2.16), SIPLUS NET CP 443-1 (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (All versions < V3.3), SIPLUS S7-300 CPU 314C-2 PN/DP (All versions < V3.3.16), SIPLUS S7-300 CPU 315-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 315F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317-2 PN/DP (All versions < V3.2.16), SIPLUS S7-300 CPU 317F-2 PN/DP (All versions < V3.2.16), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), Softnet PROFINET IO for PC-based Windows systems (All versions). Responding to a PROFINET DCP request with a specially crafted PROFINET DCP packet could cause a denial of service condition of the requesting system.
The security vulnerability could be exploited by an attacker located on the same Ethernet segment (OSI Layer 2) as the targeted device. A manual restart is required to recover the system.
What kind of flaw is it?
- CWE-20Improper Input Validation
How an attack on it works
Read straight from its severity rating, translated out of the shorthand.
- Where an attacker can beOn the same local network
- How hard it is to pull offEasy: no special conditions
- Login needed firstNo login needed
- Does someone have to clickNo, nobody has to do anything
- What an attacker getsCan take it offline
Severity vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Is CVE-2018-4843 being exploited? Not that we know of.
It is not on the list of flaws known to be exploited today. The latest forecast puts the chance of it being used in the next 30 days at 0.5%. That can change at any time, which is why we keep watching.
Timeline
- Published
- Record last updated
CVE-2018-4843 scores 25. Action: Monitor.
We keep the score of every published flaw up to date as the evidence changes. Four things go into the score, and evidence that criminals are actually using it counts most. In order:
- Evidence it is being exploitedBiggest factor
- How severe it isStrong factor
- How widely exposed it isSmaller factor
- Threat activity around itSmaller factor
85 and above is Critical. Anything confirmed as exploited is always marked for an emergency patch, whatever its score.
When CVE-2018-4843 matches software you track, it lands in your list with its score and the reasons behind it.
See your own ranked list →Who is affected by CVE-2018-4843? 22 products.
The published record lists 22 products from 1 vendor. Versions are shown as published: "before 1.7.0" means every version up to, but not including, 1.7.0. If you run one of these, check your version, then go to the fix below.
- Hardware
Simatic Cp 343-1
by Siemens
Affected versionsversion not specified - Operating system
Simatic Cp 343-1 Firmware
by Siemens
Affected versionsversion not specified - Hardware
Simatic Cp 443-1
by Siemens
Affected versionsversion not specified - Operating system
Simatic Cp 443-1 Firmware
by Siemens
Affected versionsversion not specified - Hardware
Simatic S7-1500
by Siemens
Affected versionsversion not specified - Operating system
Simatic S7-1500 Firmware
by Siemens
Affected versionsbefore 1.7.0 - Hardware
Simatic S7-300
by Siemens
Affected versionsversion not specified - Operating system
Simatic S7-300 Firmware
by Siemens
Affected versionsversion not specified - Hardware
Simatic S7-400 H V6
by Siemens
Affected versionsversion not specified
How do I fix CVE-2018-4843? Four steps.
- Check whether you run itCompare your versions with the affected products above. Not sure what you run? Precursor Intelligence can work it out from your public website, or you can pick it from a list.
- Apply the vendor’s fixInstall the update named in the vendor’s advisory. We’ve put the advisory first in the list.
- If you can’t patch todayFollow any mitigation the vendor publishes, and limit who can reach the affected system from the internet until the update is in.
- Keep an eye on itTrack the product and we tell you as soon as we spot this flaw on the list of exploited flaws, or a jump in its exploit likelihood.
References
1 linkDoes CVE-2018-4843 affect you? We'll keep checking.
Looking flaws up one at a time doesn't scale. Tell us what you run once, and we tell you which flaws matter to you, in what order, and keep watching for new ones.
- Tell us what you runPick your software from a list, or let us work it out from your website.
- We match it to every flawOver 400,000 published flaws, checked against your list.
- Ranked by real-world riskA 0 to 100 score, led by evidence criminals are using it.
- Told as soon as we knowAn alert by email, in the app or by webhook to your own tools.
Free plan, no card needed. Nothing to install.
1 new flaw affects software Acme tracks
A vulnerability has been identified in SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3),...
- Matched to
- Simatic Cp 343-1 on Acme's software list
- What to do
- Plan in the vendor’s update
Sent to the alert recipients Acme chose. Also in the app and to Acme's webhook.
CVE-2018-4843 is a medium-severity flaw in Simatic Cp 343-1 from Siemens, published on 20 March 2018. An attacker has to be on the same local network without logging in, and nobody has to click anything. If it works, the attacker can take it offline.
It scores 6.5 out of 10 on the CVSS severity scale, which is medium. Our risk score for CVE-2018-4843 is 25 out of 100, which is Low. Its action is "Monitor". No sign of exploitation and a low forecast. Patch it in your normal update cycle.
It is not on the list of flaws known to be exploited today. The latest forecast puts the chance of it being used in the next 30 days at 0.5%. That can change at any time, which is why we keep watching.
For Simatic Cp 343-1 from Siemens: version not specified. The record lists 22 products in all, each with its versions, under "Who is affected" on this page.
Install the update the vendor names in its advisory, linked first under "How do I fix" on this page. If you can't patch today, follow the vendor's mitigation and limit who can reach the affected system from the internet.